| SO |
Temp. solar |
Temperature solar (collector). Not linked: the block
calculates with 0 °C, the pump stays off. |
PU
|
Temp. buffer bottom
|
Temperature buffer bottom. Not linked: the block
calculates with 0 °C and charges the bottom permanently. This sensor
must be linked. |
PO
|
Temp. buffer top
|
Temperature buffer top. Not linked: the block
calculates with 0 °C and then always charges the top. This sensor must
be linked.
|
PU
|
Pump
digital
|
Pump digital on/off. |
PA
|
Pump
analog 0-100%
|
Pump analog. As an alternative to
control via switching hysteresis, a pump with
analog control can be used at this output.
|
| VP |
Valve buffer top |
Valve switchover buffer charging: 1 = buffer top, 0 = buffer bottom. |
|
System protection from collector
|
System protection, always active (formerly Solar max.; an existing value is kept). Above this collector temperature the pump is switched off because the solar fluid would evaporate, even if the storage is not yet reached. It starts again only when the collector is below it by the reset difference (see additional functions). |
|
Buffer maximum |
Switch-off temperature buffer. If the temperature buffer
top or bottom exceeds this value, the solar pump is switched off. |
|
Hysteresis
solar on
|
Difference between solar and buffer
at which the control becomes active.
|
|
Hysteresis
solar off
|
Difference between solar and buffer
at which the control becomes inactive. |
|
Gain |
Control setting; the higher the value, the faster the
analog output changes with a change in temperature. |