| S1 |
Temp. collector 1 |
Temperature collector field 1. Must be linked. |
| S2 |
Temp. collector 2 |
Optional. Temperature of collector array 2. Not linked: pump P2 stays off, the block works with one array. |
| WP |
Temp. exchanger primary |
Flow of the heat exchanger (solar side). Determines
the diverter valve and the speed of the exchanger pump. Must be
linked. |
| WS |
Temp. exchanger secondary |
Optional. Exchanger flow (buffer side), only shown in the status text. Not linked: the status text shows the primary flow only. |
| PU |
Temp. buffer bottom |
Must be linked. |
| PO |
Temp. buffer top |
Must be linked. |
| SP |
Lock (manual) |
Optional. Not equal to 0 locks: all outputs go to 0 once, then the block sends nothing more (manual mode). Changing to 0 releases, the block evaluates immediately. Not linked: never locked. |
| P1 / A1 |
Pump collector 1 |
On/off or speed 0-100 %. |
| P2 / A2 |
Pump collector 2 |
On/off or speed 0-100 %. |
| PT / AT |
Pump exchanger/buffer |
Secondary pump on/off or speed 0-100 %. |
| VU |
Diverter valve |
0 = buffer top, 1 = buffer bottom. |
| ST |
Status text |
State as plain text, e.g. "laedt oben: K1 64%,
K2 0%, Tauscher 70% (58.2/52.0 C)" (German text). For a text
address (14 byte). |
|
System protection from collector |
System protection, always active (formerly Solar max.; an existing value is kept). Above this collector temperature the pump is switched off because the solar fluid would evaporate, even if the storage is not yet reached. It starts again only when the collector is below it by the reset difference (see additional functions). |
|
Buffer maximum |
If both buffer sensors are above this, charging
stops. Default 85 °C. |
|
Switch-on difference |
Collector versus the colder buffer sensor, above
which the pump starts; also the threshold of the diverter valve.
Default 10 K. |
|
Switch-off difference |
Below this the pump switches off. Limited to the
switch-on difference. Default 5 K. |
|
Gain |
Speed in % per Kelvin of difference. Default
4 %/K. |
|
Minimum speed |
Lower limit of a running pump. Default
12 %. |
|
Switch-over delay bottom |
How long the exchanger flow must be too cold for
the top before the valve switches to the bottom. Default
15 s. |