Solar 2
Boiler/Buffer| This
function block realizes a solar control with two
solar circuits (e.g. two collector fields) and switching between
boiler and buffer. Each solar circuit has its own pump
(digital); a shared switchover valve determines whether the currently
charged storage tank is the boiler or the buffer. Switchover valve (VB): As long as one of the two collectors is warmer than the boiler by the Hysteresis boiler-solar on and the boiler has not yet reached its maximum, the valve switches to boiler (VB = 1). Otherwise (both collectors below the Hysteresis boiler-solar off or boiler full) it switches to buffer (VB = 0). Pump solar 1 and pump solar 2 switch on independently of each other when the respective collector temperature is warmer than the active storage tank by the hysteresis belonging to the active storage tank (boiler-solar or buffer-solar) and its maximum is not reached. They switch off when the difference falls below the threshold or the storage or solar maximum temperature is reached. Between the switch-on and switch-off threshold the last state is kept, so the switch-on hysteresis must be greater than the switch-off hysteresis. Both collector circuits always charge into the same storage tank - the valve applies to both. This block controls the pumps digitally only, there is no speed output. The control runs once per second. |
Inputs |
||
| BU | Temp. boiler | Temperature boiler (bottom). Not linked: the block calculates with 0 °C, the boiler is therefore regarded as cold and the valve stays on boiler permanently. This sensor must be linked. |
| PU |
Temp. buffer |
Temperature buffer (bottom). Not linked: the block calculates with 0 °C. This sensor must be linked. |
| S1 |
Temp. solar 1 |
Temperature solar 1 (collector 1). Not linked: the block calculates with 0 °C, pump solar 1 stays off. |
| S2 |
Temp. solar 2 |
Temperature solar 2 (collector 2). Not linked: the block calculates with 0 °C, pump solar 2 stays off. If only one collector array is used, leave this input free. |
Outputs |
||
| VB |
Valve boiler |
Valve switchover boiler/buffer: 1 = boiler, 0 = buffer. |
| P1 |
Pump solar 1 |
Pump solar circuit 1 on/off. |
| P2 |
Pump solar 2 |
Pump solar circuit 2 on/off. |
Parameters |
||
| System protection from collector |
System protection, always active (formerly Solar max.; an existing value is kept). Above this collector temperature the pump is switched off because the solar fluid would evaporate, even if the storage is not yet reached. It starts again only when the collector is below it by the reset difference (see additional functions). | |
| Buffer
max. |
Switch-off temperature buffer. If the buffer temperature exceeds this value, buffer charging is ended. | |
| Boiler
max. |
Switch-off temperature boiler. If the boiler temperature exceeds this value, boiler charging is ended. | |
| Hysteresis
buffer-solar on |
Difference between solar and buffer
at which buffer charging becomes active. |
|
| Hysteresis
buffer-solar off |
Difference between solar and buffer at which buffer charging becomes inactive. | |
| Hysteresis
boiler-solar on |
Difference between solar and boiler at which switching to boiler charging is performed. | |
| Hysteresis
boiler-solar off |
Difference between solar and boiler at which boiler charging becomes inactive. | |