| UE |
Surplus in watts |
Optional. A value at or above the recommendation or start threshold
switches to state 3 or 4 once it has been present for the minimum duration. Whether a
positive or a negative value is surplus is set by the parameter Surplus is. Not
connected: there is never surplus, the block stays in normal operation. |
| SB |
Block command grid operator |
Optional. Not 0 blocks (state 1), 0 releases. Applies as long as the
value is present. Not connected: never blocked. |
| AN |
Heat request |
Optional. Bit of the heat request of a consumer (heating circuit, hot
water, collector). Not 0 counts as a request whose temperature AT may then exceed the
base value heating. Not connected: only AT counts - a temperature above 0 counts as a
request. |
| AT |
Heat request temperature |
Optional. Temperature wanted by the consumer. Acts only while a request is
present: if it is higher than the base value heating, it becomes the base value. Not
connected: the base value stays unchanged. |
| TP |
Buffer temperature |
Optional. Basis of the buffer limit and of the end of the preload. Not
connected: no buffer limit, the preload runs as long as VF is present. |
| SO |
Setpoint heating (base value) |
Optional. Not connected or 0: the parameter Base value heating
applies. |
| SW |
Setpoint hot water (base value) |
Optional. Not connected or 0: the parameter Base value hot water
applies. |
| BA |
Mode |
Optional. 0 automatic, 1 normal operation only (no surplus), 2 blocked, 3
force start command. An unknown value counts as automatic. Not connected:
automatic. |
| SM |
Fault signal heat pump |
Optional. Not 0 reports a fault; it counts only once it has been present
longer than the fault signal delay. Then SR is 1 and the block goes to normal
operation. Not connected: a fault is never detected. |
| FR |
Enable |
Optional. 0 takes away the surplus use of the block: it stays in normal
operation. The block of the grid operator still applies. Not 0 enables. Not connected:
the block counts as enabled. Use this input if another consumer is to have
priority. |
| VF |
Preload enable |
Optional. Not 0 reports the time window before a block. Acts only if the
parameter Preload is on. Not connected: no preload. |
| K1 |
Contact 1 |
Contact 1 of the enable interface, according to state and parameters. |
| K2 |
Contact 2 |
Contact 2 of the enable interface, according to state and parameters. |
| ZU |
State |
1 block, 2 normal operation, 3 recommendation, 4 start command. |
| SH |
Setpoint heating |
Base value, raised and limited if applicable. To the device or to the
Modbus master. |
| SS |
Setpoint hot water |
Base value, raised and limited if applicable. To the device or to the
Modbus master. |
| VL |
Preload running |
1 during the preload. |
| GS |
Blocked |
1 in the block state. |
| ST |
Status text |
State in plain text (in German, ASCII, written by the runtime). For a text
address. |
| SR |
Fault |
1 with a fault signal of the heat pump and with a block that lasts longer
than the block maximum duration. |
| BT |
Operating hours surplus use |
Hours in the states recommendation and start command. Survives a restart
of the controller. |
|
Contacts block / normal operation / recommendation / start command |
Which contacts are closed in the state. Default according to the standard:
block contact 1, normal operation open, recommendation contact 2, start command
both. |
|
Invert contact 1 / 2 |
Inverts the output, for devices with a normally closed contact. Default
off. |
|
Surplus is |
Positive or negative (grid power measurement, feed-in negative). Default
positive. |
|
Surplus hysteresis |
A state is left only when the surplus falls below its threshold by this
value. Default 200 W. |
|
Recommendation: threshold, minimum duration, raise heating/hot water |
Default 1000 W, 5 min, 3 K and 3 K. Threshold 0
switches the recommendation off. |
|
Start command: threshold, minimum duration, raise heating/hot water,
daily budget |
Default 2500 W, 5 min, 5 K, 7 K and 240 min.
Threshold 0 switches the start command off, budget 0 = unlimited. |
|
Block maximum duration, block on exceeding |
If the block of the grid operator lasts longer, SR reports a fault. "Report
only" keeps the block, "End block" lifts it - the block then works on the surplus again.
Default 0 = unlimited, report only. A block through the mode is never limited. |
|
Preload, raise buffer |
Default off, 5 K. |
|
Minimum run time per state, minimum pause |
Default 10 min and 5 min. |
|
Base value heating / hot water |
Apply as long as SO or SW are not connected. Default 35 °C and
48 °C. |
|
Maximum setpoint heating / hot water |
Limits the setpoint including the raise. Default 60 °C. 0 = no
limit. |
|
Buffer maximum temperature |
Default 60 °C. 0 = no limit. Acts only with input TP
connected. |
|
Fault signal delay |
Default 60 s. |