EASEE charging station| With
this function block the EASEE charging station is
controlled so that only the PV surplus is charged. Important: This block is intended for test purposes only, as the API for third-party providers has not yet been released by the manufacturer. |
Inputs |
||
| BA |
Operating mode* |
Operating mode:
|
| LM |
Charging current
manual A |
Charging current setpoint operating mode manual |
| PU |
Surplus* |
PV surplus. The input must not be limited to 0; both positive and negative values must arrive at the input so that the control can react correctly. With the parameter Type surplus it can be set whether positive or negative means surplus. |
| SU | Start surplus limit value | Via this input a limit value for the surplus control can be specified. This limit value must be exceeded for the charging control to begin. |
| SZ | Start surplus time s | Time that the surplus must be above the limit value for the control to begin. |
| UM | Surplus minimum | Minimum surplus. The charging station is controlled so that this minimum remains as surplus. E.g. when consumers are switched on briefly. |
Outputs |
||
| ST |
Status |
|
| LS | Surplus charging active | Output is 1 when the control is active. |
| SS | Charging current setpoint | Setpoint that is sent to the charging station. |
Parameters |
||
| User name |
User name EASEE account | |
| Password | Password EASEE account | |
| Charging station ID | ID charging station | |
| Gain
P |
Speed of the control; with a higher value the output reacts faster to a change at the input. | |
| Type surplus | PV surplus positive or negative | |
| Start at surplus | Charging is only started above this power | |
| Control on/off time | Time that the surplus must be present for charging to start or be interrupted. | |
| Surplus minimum | The control is managed so that at least this surplus still remains present. | |
| Charging current
minimum |
Minimum charging current |
|
| Charging current maximum |
Maximum charging current | |