| TO |
Buffer temperature top |
Mandatory input. Not connected or outside -50 to 150 °C: fault, no
reload. |
| TM |
Buffer temperature middle |
Optional. Counts into the charge level and, depending on the setting, into reload
and end of charging. Not connected: the sensor is ignored. |
| TU |
Buffer temperature bottom |
Optional. Like TM; also the reference of layered charging. Not connected: the sensor
is ignored. |
| AN |
Request consumers |
Optional. Bit of the heat request. Not 0 requests. Not connected: only AT counts - a
temperature above 0 counts as a request. |
| AT |
Request consumers temperature |
Optional. Wanted temperature. Not connected or 0: the parameter request without
temperature applies. |
| FQ |
Foreign heat source active |
Optional. Not 0: another source is charging. Not connected: there is no foreign
source. |
| FR |
Enable |
Optional. 0 blocks the reload, not 0 enables. Not connected: the block counts as
enabled. |
| SP |
Lock |
Optional. Not 0 blocks the reload, 0 enables. Not connected: never locked. |
| AN |
Request to the generator |
1 during the reload. |
| AT |
Request to the generator temperature |
Request plus charge offset during the reload, otherwise 0. |
| LP |
Charge pump generator |
1 during the reload. |
| UO |
Diverter valve layered charging top |
1: charge at the top. Only with layered charging and during the reload. |
| EF |
Discharge enable |
1: the consumers may draw from the buffer. |
| LZ |
Charge level in % |
0 to 100 %, from the available sensors. |
| EN |
Usable energy in kWh |
Estimate, see above. |
| UW |
Excess heat removal active |
1 as long as the buffer top is above the limit temperature. |
| ST |
Status text |
State in plain text (German, ASCII, written by the runtime), for example "Puffer 44 %,
deckt die Anforderung". For a text address. |
| SR |
Fault |
1 with a missing or implausible top sensor. |
|
Volume, reference temperature 0 % and 100 % |
Default 1000 l, 25 ° and 70 °. |
|
Sensor for reload, sensor for end of charging |
Default top and middle. A sensor that is not connected is replaced by the top one
or the reload sensor. |
|
Switch-on difference, switch-off difference, charge offset |
Default 2 K, 6 K and 5 K. The switch-off difference must be larger
than the switch-on difference. |
|
Request without temperature |
Default 45 °C. |
|
Minimum charge time, minimum pause |
Default 5 min each. |
|
Layered charging, top below, switching delay |
Default off, 40 ° and 60 s. |
|
With foreign source, lowering of switch-on threshold, run-on |
Default "block reload", 5 K and 10 min. |
|
Excess heat removal, from, reset difference |
Default off, 90 ° and 5 K. |
|
Discharge enable minimum temperature |
Default 0 = off. |